Model Of The Soft Starter
Data-sheet
Soft starter | Rated motor power | Model | |||
Soft Starter | Working Max | 220V | 380V | 660V | Please refer to |
WSTR3007 | 15 | 4KW | 7.5KW | 11KW | R1 |
WSTR3011 | 23 | 5.5KW | 11KW | 15KW | |
WSTR3015 | 31 | 7.5KW | 15KW | 22KW | |
WSTR3018 | 38 | 9KW | 18.5KW | 30KW | |
WSTR3022 | 44 | 11KW | 22KW | 37KW | |
WSTR3030 | 60 | 15KW | 30KW | 45KW | |
WSTR3037 | 74 | 18.5KW | 37KW | 55KW | |
WSTR3045 | 100 | 22KW | 45KW | 75KW | |
WSTR3055 | 110 | 30KW | 55KW | 90KW | |
WSTR3075 | 150 | 37KW | 75KW | 115KW | |
WSTR3090 | 160 | 45KW | 90KW | 132KW | R2 |
WSTR3115 | 200 | 55KW | 115KW | 160KW | |
WSTR3132 | 250 | 75KW | 132KW | 200KW | |
WSTR3160 | 300 | 90KW | 160KW | 250KW | |
WSTR3200 | 360 | 115KW | 200KW | 355KW |
Basic Functions
Meet the standards | GB14048.6/IEC 60947-2-2:2002 |
Three phase power supply | AC 380V(optional 220V and 660V) |
Frequency | 50Hz/60Hz |
Suitable motor | Squirrel cage three-phase asynchronous motor |
Start-up frequency | When the motor is fully loaded, no more than 4 times per hour, no load or light load, no more than 10 times per hour. |
Protection level | IP20 |
Anti shock | IEC68-2-27:15kg,11ms |
Seismic capacity | At an altitude of 3000 below ground gas, the vibration stresses below 0.5G |
Ambient temperature | working temperature |
Storage temperature | -25 |
Ambient temperature | 93% no condensation or drop |
Maximum work | 1000 |
Cooling mode | Natural cold wind |
Relative to vertical | Vertical installation, angle range |
External Dimensions
External dimensions of 5.5kw-75kw
Please see the below table for the external and installation dimensions of WS1R3000 series 5.5kw-75kw soft starter.
Model | Rated power (KW) | Rated current(A) | External dimensions | Installation dimensions | Net weight | ||||
H1 | W1 | D | H2 | W2 | d | ||||
WSTR 3005 | 5.5 | 11 | 310 | 155 | 175 | 296 | 127 | M6 | 5 |
WSTR 3007 | 7.5 | 15 | 310 | 155 | 176 | 296 | 127 | M6 | 5 |
WSTR 3011 | 11 | 22 | 310 | 155 | 176 | 296 | 127 | M6 | 5 |
WSTR 3013 | 15 | 30 | 310 | 155 | 176 | 296 | 127 | M6 | 5 |
WSTR 3018 | 18.5 | 37 | 310 | 155 | 176 | 296 | 127 | M6 | 5 |
WSTR 3022 | 22 | 43 | 310 | 155 | 176 | 296 | 127 | M6 | 5 |
WSTR 3030 | 30 | 60 | 310 | 155 | 176 | 296 | 127 | M6 | 5 |
WSTR 3037 | 37 | 75 | 310 | 155 | 176 | 296 | 127 | M6 | 5 |
WSTR 3045 | 45 | 90 | 310 | 155 | 176 | 296 | 127 | M6 | 5 |
WSTR 3055 | 55 | 110 | 310 | 155 | 176 | 296 | 127 | M6 | 5 |
WSTR 3075 | 75 | 150 | 310 | 155 | 176 | 296 | 127 | M6 | 5 |
Terminal Configuration Diagrams
Terminal diagram of the main circuit
1) WSTR3005-3075 | WSTR 3090-3400 |
2)Terminal diagram of the control circuit
3)Terminal connection of the control circuit
Why Choose Us
WSTRD series Motor Starter has a Chinese & English LCD display to real-time display current, voltage and other operating status. The help information can be assessed when the soft starter is not in the soft start/ soft stop status or the setting status; press Yes(button for confirmation), then press the up/down buttons to read the prompt messages.
Display | Description |
AC:XXX | Four-digit voltmeter, used to test the voltage of the three phase AC power |
XXA-XXV | Indicate the specification of the soft starter |
H1:Err0r00 | Indicate that the latest fault information is zero |
H2:Err0r00 | Indicates no occurred fault information |
H3:Err0r06 | Indicates the occurred fault information Err0r06 |
... | ... |
H9:Err0r00 | indicates no fault information |
Ver:4.2 | Indicates the software version of the product is Ver4. 2 |
LXXXX | The total times of successful starting |
T-run | Time used in last soft start(whether succeed or not) |
Note: HI-H9 saves the recent 9 fault information in the recursive method |
Connection Of The Main Circuit And The Grounding Terminal
(I) Main circuit power input terminal (R,S, T)
a.Connect the main circuit input terminals R, S, T to the three-phase AC power through the circuit breaker for circuit protection or circuit breaker with leakage protection without considering the connection sequence
b.Do not use ON/OFF of the main circuit power to control running and stop of the soft starter, instead, such should be controlled by means of the control terminal or RUN and STOP buttons in the keyboard panel of the soft starter upon power on.
c.Do not connect the soft starter to the single-phase power.
(2) Output terminals of the soft starter (U ,V ,W )
a.Output terminals of the soft starter should be connected to the three-phase motor in correct phase sequence. If the rotation direction of the motor is incorrect, switch connection of any two phases among U, V and W.
b.The output end of the soft starter shall not be connected to capacitor or surge absorber.
c.If the wire between the soft starter and the motor is very long, the distributed capacitance between the wires will generate highfrequency current which may cause over-current tripping, leakage current increasing and poor current display precision of the soft starter. Therefore, it is suggested that the motor connection wire should be no more than 50m.
(3) Grounding terminal of the soft starter (〨 G)
a.For safety and noise reducing, the grounding terminal G of the soft starter must be well-grounded. To prevent electric shock and fire accidents, the metal enclosure and frame of the electric equipment should comply with the requirements of the national electronic procedures.
Description Of Protection Functions
WSTR 3000 series soft starter possesses complete protection functions to protect the operation security of the soft starter and the motor. During operation, the protection level and protection parameters should be properly set base don different circumstances.
● Over-heating protection of the soft starter: the protection will start when the temperature rises to 80℃±5℃, and it will stop when the temperature falls to 55℃(lowest).
● Delayed time of input phase loss protection: <3s.
● Delayed time of output phase loss protection: <3s.
● Delayed time of input three-phase unbalance protection: <3s. Taking the deviation of current in each phase is over 50%10% as the criteria, when the load current is less than 30% of the nominal rated value of the soft starter, it is confirmed that the deviation will increase.
● Protection time of over-current during starting: the protection time shall be continued to be longer than 5 times of the maximum operating current of code F5,
● Delayed time for power under-voltage protection: when the power voltage is under the extreme value 40%, the protection time< 0.5s, when the power voltage is below the set value, the protection time< 3s.
● Delayed time for power over voltage protection: when the power voltage is over the extreme value 130%, the protection time< 0.5s, when the power voltage is over the set value, the protection time< 3s.
● Delayed time for load short circuit protection < 0.1 s, if the current is more than IO times of the nominal rated value of the soft starter, this protection shall not replace the fuse or short circuit protection device.
The above time parameters are the periods from the valid signal being detected to the tripping protection directive being given; these parameters are for information only. In the event that the protection functions of the soft starter fails to meet the requirements of customers, special protection devices should be installed to ensure the safety.
Technical Characteristics
1.Unique SCR trigger closed-loop control algorithm
Unique SCR closed-loop control, specially designed for standard and heavy loads. The user can select the current limit start and the voltage ramp start according to the load condition to achieve an absolutely smooth torque-free oscillation start effect.
2.Control accuracy, real-time efficiency
High-performance CORETX-M3 32-bit core CPU for center control, fast speed, high precision, strong anti-interference ability
3.Beautiful appearance
Patented main circuit three-in and six-out structure, built-in current transformer scheme, convenient wiring and high reliability
4.Optional standard MODBUS-RTU protocol
Integrated advanced protection.It has protection functions such as input and output phase loss, overload, overcurrent, phase current imbalance, thyristor over temperature, etc., to protect the motor and related equipment in all directions.
5.Full refractory
90kw or less is a fully molded shell structure, processed with flame-retardant ABS material. The upper cover of 90KW and above is made of plastic shell structure, and the main frame is made of aluminum-zinc plate material. It has heat resistance and corrosion resistan
6.CE.
7.External lead panel
The panel can be externally led to the operating surface of the device for remote operation through the fuselage interface, which is convenient for on-site use.
8.Simple maintenance
A monitoring signal coding system consisting of a 4-digit digital display that monitors the operating conditions of system equipment 24 hours a day, while providing fast fault diagnosis
About Us
● Established in 2010 ,Winston Electric Co.,LTD, is a professional manufacturer and exporter that is concerned with the design, development and production of Inverter ,Motor soft Starter, Speed Control, Transformer,Circult Breaker, etc. We are located in Wenzhou City Zhejiang Province, with convenient transportation access. All of our products comply with international quality standards and are greatly appreciated in a variety of different markets throughout the world. Our well-equipped facilities and excellent quality control throughout all stages of production enables us to guarantee total customer satisfaction. Besides, we have received ISO9001, TUV and CE. As are suit of our high quality products and outstanding customer service.
● With special cultivation of employees, high investment on production facilities and R&D as well as a wide range of products, we advocate "technology innovation, business honesty and trust and quality first" as our basic principle, trying to develop into a world-class electrical manufacturer with constant efforts.
● The company has a rigorous experimental team to develop and produce the latest and most practical products
● Mainly occupied the international market. Exported to Southeast Asia , Europe ,North America , Australia ,Middle East and other countries and regions ,enjoy a high reputation in the world.
● If you need any help, please contact us immediately. And we would be very grateful if you have any comments.
FAQ
Q: Do you have you own factory?
A: Yes! All of our products are supplied directly from our factory. Yueqing Winston Electrical Equipment Co.,Ltd who is professional manufacturing soft starter, transformer and power switch etc for more then 10 years. So the price is very competitive.
Q: Why choose us ?
A: 1. Famous brand in china for 10 more years ---- Winston
2. Easy operating system ---- Easy but effective software, gentle touch achieves
3. Stable performance ---- best famous compenents ensure the quality all the time
4. Excellent aftersales service ---- 24*7 hours online serive, never leave you alone.
5. Fast delivery ---- cheap & safe delivery, we look after it all the time
Q: How do I choose the size of the soft starter?
Different types of load demand for power are different. You can view the load power values to determine the size of the power soft starter.