Model Of The Soft Starter
Data-sheet
Soft starter | Rated motor power | Model | |||
Soft Starter | Working Max | 220V | 380V | 660V | Please refer to |
WSTR3090 | 160 | 45KW | 90KW | 132KW | R2 |
WSTR3115 | 200 | 55KW | 115KW | 160KW | |
WSTR3132 | 250 | 75KW | 132KW | 200KW | |
WSTR3160 | 300 | 90KW | 160KW | 250KW | |
WSTR3200 | 360 | 115KW | 200KW | 355KW |
Basic Functions
Meet the standards | GB14048.6/IEC 60947-2-2:2002 |
Three phase power supply | AC 380V(optional 220V and 660V) |
Frequency | 50Hz/60Hz |
Suitable motor | Squirrel cage three-phase asynchronous motor |
Start-up frequency | When the motor is fully loaded, no more than 4 times per hour, no load or light load, no more than 10 times per hour. |
Protection level | IP20 |
Anti shock | IEC68-2-27:15kg,11ms |
Seismic capacity | At an altitude of 3000 below ground gas, the vibration stresses below 0.5G |
Ambient temperature | working temperature |
Storage temperature | -25 |
Ambient temperature | 93% no condensation or drop |
Maximum work | 1000 |
Cooling mode | Natural cold wind |
Relative to vertical | Vertical installation, angle range |
External Dimensions
External dimensions of 90kw-400kw
Please see the below table for the external and installation dimensions of WSTR3000 series 90kw-400kwsoft starter.
Model | Rated power (KW) | Rated current(A) | External dimensions | Installation dimensions | Net weight | ||||
H1 | W1 | D | H2 | W2 | d | ||||
WSTR 3090 | 90 | 180 | 400 | 270 | 240 | 355 | 244 | M8 | 18 |
WSTR 3115 | 115 | 230 | 400 | 270 | 240 | 355 | 244 | M8 | 18 |
WSTR 3132 | 132 | 264 | 400 | 270 | 240 | 355 | 244 | M8 | 18 |
WSTR 3160 | 160 | 320 | 400 | 270 | 240 | 355 | 244 | M8 | 18 |
WSTR 3200 | 200 | 400 | 400 | 270 | 240 | 355 | 244 | M8 | 18 |
WSTR 3250 | 250 | 500 | 455 | 300 | 265 | 395 | 265 | M8 | 28 |
WSTR 3280 | 280 | 560 | 455 | 300 | 265 | 395 | 265 | M8 | 28 |
WSTR 3320 | 320 | 640 | 455 | 300 | 265 | 395 | 265 | M8 | 28 |
WSTR 3400 | 400 | 800 | 455 | 300 | 265 | 395 | 265 | M8 | 28 |
Terminal Configuration Diagrams
Terminal diagram of the main circuit
1) WSTR3005-3075 | WSTR 3090-3400 |
2)Terminal diagram of the control circuit
3)Terminal connection of the control circuit
Why Choose Us
Yueqing Winston Electric CO.,LTD has made further technical improvement in both the software and the structure of the soft starter according to the market demand. The soft starter provides complete motor protection functions including start control, running and overloading, phase failure, three-phase unbalance, over-voltage, under-voltage protection and so on. As another great achievement in the intelligentization of motor protection and networked technology application, it simplifies the circuit, reduces the volume, cuts the coat, makes installation and using more convenient.
Installation direction and space: to enable good ventilation and heat dissipating conditions during using of the soft star ter, the soft starter should be installed vertically with enough space for heat dissipating left around the equipment. The allowable minimum spaces are shown in figure 2.1 and figure2.2.
In the event that the soft starter is installed inside the cabinet, besides the above requirements, the cabinet selected should be with good ventilation at the top and bottom, as shown in figure 2.3.
Through the inbuilt RS485 standard interface, WSTR 3000 series soft starter can connect with PC and PLC and other hosts to conduct serial communication. The command of the host can control running or stop of the soft starter, monitor the running status of the soft starter and modify its functional data.
Major functions
1.Input of stop running command.
2.Monitoring of the running status
3.Real-time tracking (tabular display of the running information)
4.Read-once, write-once and saving to files of function codes. Please consult our company separately for the communication software.
Connection Of The Main Circuit And The Grounding Terminal
(I) Main circuit power input terminal (R,S, T)
a.Connect the main circuit input terminals R, S, T to the three-phase AC power through the circuit breaker for circuit protection or circuit breaker with leakage protection without considering the connection sequence
b.Do not use ON/OFF of the main circuit power to control running and stop of the soft starter, instead, such should be controlled by means of the control terminal or RUN and STOP buttons in the keyboard panel of the soft starter upon power on.
c.Do not connect the soft starter to the single-phase power.
(2) Output terminals of the soft starter (U ,V ,W )
a.Output terminals of the soft starter should be connected to the three-phase motor in correct phase sequence. If the rotation direction of the motor is incorrect, switch connection of any two phases among U, V and W.
b.The output end of the soft starter shall not be connected to capacitor or surge absorber.
c.If the wire between the soft starter and the motor is very long, the distributed capacitance between the wires will generate highfrequency current which may cause over-current tripping, leakage current increasing and poor current display precision of the soft starter. Therefore, it is suggested that the motor connection wire should be no more than 50m.
(3) Grounding terminal of the soft starter (〨 G)
a.For safety and noise reducing, the grounding terminal G of the soft starter must be well-grounded. To prevent electric shock and fire accidents, the metal enclosure and frame of the electric equipment should comply with the requirements of the national electronic procedures.
About Us
● Established in 2010 ,Winston Electric Co.,LTD, is a professional manufacturer and exporter that is concerned with the design, development and production of Inverter ,Motor soft Starter, Speed Control, Transformer,Circult Breaker,etc. We are located in Wenzhou City Zhejiang Province, with convenient transportation access. All of our products comply with international quality standards and are greatly appreciated in a variety of different markets throughout the world.Our well-equipped facilities and excellent quality control throughout all stages of production enables us to guarantee total customer satisfaction.Besides, we have received ISO9001,TUV and CE..As are suit of our high quality products and outstanding customer service.
● With special cultivation of employees, high investment on production facilities and R&D as well as a wide range of products, we advocate "technology innovation, business honesty and trust and quality first" as our basic principle, trying to develop into a world-class electrical manufacturer with constant efforts.
● We can provide customized service we are a customer oriented manufacturer our products can be customized.
● Electronic products require a regular and appropriate maintenance schedule to operate reliably and economically over a long period of time. They need to have regular servicing and replacement of worn out parts. For all such maintenance we have a separate team which is specialized in scheduled and breakdown maintenance for our products. Our teamis passionate about its business which positively reflects in our assertive approach to sales and customer service.
● We are an ISO9001:2000 certified company. We have obtained many certificates, such as CCC, CE, CB, GS and RoHS. Stability, expertise and technological innovation are the core stones of our business strategy. Aiming at reliable product quality and the highest customer satisfaction, we are consistently deepening enterprise inner reform and fully carry out a quality guarantee system.
FAQ
Q: What information should be provided to get a clear model with quotation?
A: Please directly provide input voltage, your requirements and usage occasion or our models.
Q: What's your quality control system?
A: We have strict quality control system, and each product is done fatigue testing, calibration, temperature compensation before shipment. High quality is guaranteed.
Q: How does your factory carry out quality control?
A: Quality is priority. Winston people always attaching great importance to quality controlling from the very beginning to the end. We have professional QC team to carry out the Quality control.
Q: How to choose a right system and products?
A: Leave it to us! Tell us your requirements, then our seller will recommend a suitable product and system to you.
Q: Why choose us?
A: Winston have been engaged in new energy power generation for more than 10 years. Our products and services cover more than 60 countries. Our R&D team is composed of top experts in various fields. We are committed to providing first-class solutions for PV power plants.